The alarm sounded, why didn't the workers run away? ——Labor intensive enterprise fire safety undercover investigation

2026-08-17 08:58

Yin Wenzhuo, a reporter from Zhonggong Net

Do you know what sound this is? "" Why aren't you running

In mid July, the Ministry of Emergency Management, the National Fire and Rescue Bureau, together with the Ministry of Industry and Information Technology, the Ministry of Natural Resources, and the State Administration for Market Regulation, organized a special undercover inspection of fire safety in labor-intensive enterprises. When the undercover investigation team pressed the manual fire alarm button in the workshop, sharp and piercing fire alarms sounded repeatedly. The workers looked up and continued to work with their heads down. The reporter found that this phenomenon is not an isolated case.

During the multi day undercover investigation, the reporter accompanied several labor-intensive textile and clothing enterprises. In workshops with as few as dozens or as many as hundreds of people, scenes of firefighting facilities operating with illnesses, evacuation routes in name only, and on duty personnel feeling helpless in the face of a fire repeatedly occur

Fire control room 'hollowing out': If there is a fire, who will take care?

The fire control room, known as the "brain" of enterprise fire safety management, is responsible for receiving and processing fire alarm information in the early stages of a fire, activating fire pumps after confirming the fire situation, and guiding personnel evacuation. However, in undercover investigations, this "brain" is in a state of "brain death" in many companies - the on duty personnel do not understand the operation or are simply not on duty.

The undercover investigation team pushed open the door to the fire control room of Shaoxing Xianghua Knitting Co., Ltd. and found that there were no fire facility operators on duty. The relevant person in charge of the enterprise said, 'The on duty personnel just had something to do at home and went to have dinner.'. Not only that, multiple alarm signals on the fire control equipment continued from noon to evening without any alarm sounds.

Last year, we arranged for our staff to take two exams (Fire Facility Operator Certificate). As soon as they obtained the certificates, they demanded a salary increase and left without reaching an agreement. The relevant person in charge of Gongqingcheng Export Clothing Industry Park said that the company has sent people to take the exams again, but the exam cycle is long, and the fire control room is still in a vacuum period of "having equipment but not qualified personnel on duty".

If the previous question is' Is there anyone here? ', the issue of the Yudu County Industrial Park Returning Home Entrepreneurship Park in Jiangxi Province is' There are only people here.'. After the undercover investigation team pressed the manual alarm button in the workshop, the equipment in the fire control room did not emit any alarm sound. After inspection, it was found that the alarm broadcast connection line had been manually unplugged. Faced with the requirement to manually operate the emergency broadcast, the on duty personnel and security guard were unable to switch successfully after a long time of operation. Faced with inquiries from the undercover investigation team about operating procedures, the on duty personnel frequently choked up and glanced at the "Fire Safety Management System" and "Fire Emergency Plan Fire Extinguishing Flow Chart" posted on the wall in search of answers.

This situation is not an isolated case. At Jiaxing Huishun Textile Dyeing and Finishing Co., Ltd., when the undercover investigation team arrived at the fire control room, only one unlicensed and inexperienced employee was temporarily on duty. After making a phone call, the licensed duty personnel were called in. However, this certified personnel is not only unfamiliar with the fire alarm disposal process, but also does not know how to operate the host, and does not know how to reset system faults. Whenever the undercover investigation team further inquires, the employee will reply with "just signed the fire maintenance contract" and "waiting for the maintenance unit to handle it".

In different locations and enterprises, the fire control room presents the same situation: some people are unlicensed, some are unlicensed, and even if they know, they may not be on duty. Behind each "hollowed out" fire control room, there are dozens or even hundreds of workers with no one to guard the fire safety.

Escape route 'obstruction': doors locked, roads blocked, windows sealed

With so many people working, how can this door escape in case of a fire

At Shaoxing Keqiao Muyulin Textile Factory, the undercover investigation team found that there was only one safety exit in the workshop. Dozens of workers in the workshop are busy, and once a fire breaks out, everyone must squeeze towards the same exit; If a fire breaks out near the exit, workers will find it almost impossible to escape. Faced with inquiries, the company leader did not answer.

The fire escape is the lifeline for workers during a fire. Every time they visit a company, the first thing the undercover investigation team notices is the fire escape route. Among them, many enterprises not only fail to set up and use escape doors in accordance with regulatory requirements, but also turn evacuation staircases into storage and stocking rooms. At Jiangxi Gongqing Chengyuan Cheng Clothing Co., Ltd., the undercover investigation team entered the workshop to inspect and then turned back, and found that the evacuation staircase had been filled with goods, making it impossible to pass through normally.

The problem of Yisha Clothing Processing Department in Honghe Town, Xiuzhou District, Jiaxing City is more typical. As soon as the undercover investigation team entered the stairwell, they saw a makeshift kitchen occupying half of the fire escape. The remaining space is only enough for one person to pass through, and in some places, it is even necessary to turn sideways to pass through. The company leader stated that a one meter wide fire escape route has been reserved for evacuation use. Not only that, there are foam boards, cartons, plastic bags, cloth and other combustibles stacked in the stairwell, even extending to the stairs.

However, at Chengming Textile Factory in Xucun Town, Haining City, a rolling shutter door was installed at the location of the safety exit. In response, the undercover investigation team explicitly stated that "rolling shutter doors cannot be used as evacuation doors". In a fire, if the rolling shutter door cannot be raised due to power failure, the escape route will be completely sealed off. The company leader stated that they were not aware of this regulation before.

The function of fire doors is to prevent the spread of fire and smoke from one area to another. As a 'safe space', stairwells must be protected by fire doors. "The undercover investigation team told reporters that fire doors must be kept closed and have standardized opening directions, and should be opened in the direction of evacuation. Once the stairwell is invaded by fireworks, people upstairs cannot come down and cannot escape

At the same time, the doors with the words "normally closed fire doors" are always open, anti-theft nets are installed on workshop windows, and safety exits are locked... Some companies turn a blind eye to these fire hazards, making it difficult to ensure the safety of workers at critical moments.

Fire protection facilities are virtually non-existent: there is no water in the fire hydrant, and the smoke detector does not have its cap removed

What is this? Is it mouse droppings

At Gongqing City Shenchang Garment Co., Ltd., when faced with inquiries from the undercover investigation team, the company leader was speechless. In a factory building of over a thousand square meters, when I casually opened an indoor fire hydrant, a musty smell came out - the water hose had already become moldy, a thick layer of dust had accumulated at the bottom of the hydrant, and even mouse feces were scattered on the fire hose.

There is a high possibility of water leakage when using a fire hydrant to extinguish the fire, "the undercover investigation team immediately judged.

According to the person in charge of the enterprise, the factory had a fire more than ten years ago. I have been feeling pain in my heart, wanting to do a good job in fire safety work, but I don't know how to do it, and the factory also lacks professional fire safety management personnel. The previous fire did not exchange for intact fire hydrants, and the workers in the workshop did not know that the fire safety facilities around them were useless.

The lack of water and insufficient water pressure in the fire hydrant were also frequently discovered during the undercover investigation. At Jiangxi Obote Clothing Co., Ltd., the undercover investigation team randomly turned on an indoor fire hydrant, and the valve rotated several times, but after two or three minutes, not a single drop of water flowed out. The relevant person in charge said, 'The pipeline in the park is under maintenance.'. During the maintenance period, dozens of workers still sit in front of the machine every day to rush orders. And the door panel of the fire hydrant box of Jiangxi Xinbang Clothing Co., Ltd. just blocks the fire hydrant interface, making it impossible to connect the water hose.

Not only are there problems with the fire hydrants, but the fire and smoke detectors are also on standby all year round. Many companies have installed point type smoke and fire detectors neatly, but have never removed the dust cover. Ganzhou Fanyibo Clothing Co., Ltd. has been in production for several months, but the smoke detection equipment in the workshop still wears red dust covers. For several months, the workers have been working tirelessly, but they have turned a blind eye to the hidden danger of smoke detectors wearing dust covers. Fire inspectors pointed out that smoke detection equipment is used to detect and perceive fire smoke. When a fire occurs, intact smoke detection equipment can detect smoke at the first time and issue an alarm signal. Without the dust cover removed, smoke detection equipment cannot detect and perceive fire smoke, which will delay the alarm time and cause the fire to spread and expand.

Some companies, for the sake of convenience or cost savings, have installed fire-fighting facilities but have not properly maintained them, making it difficult for them to play an effective role at critical moments. However, some companies' maintenance work is perfunctory and lacks timely and effective detection and repair of fire safety issues. The inspection report issued by the third-party maintenance company of Yudu Xinaobao Plastic Footwear Co., Ltd. is marked in black and white as "meets the requirements". The main unit in the fire control room cannot be used for manual or automatic broadcasting, and personnel evacuation instructions cannot be given at critical moments.

During the undercover investigation, the most common response heard by reporters was' I don't know '. In labor-intensive enterprises, 'not knowing' is often the biggest fire hazard.

Because I don't know about the point type smoke fire detector, I need to remove the dust cover. Once a dangerous situation occurs, the equipment cannot give a warning; Because I don't know how to use a fire extinguisher, I am unable to extinguish the initial fire; Because I don't know how to operate the equipment, I don't know the fire disposal process, and I can't prevent the fire from spreading and expanding

When one by one 'don't know' comes together, it forms the opening problem: the fire alarm sounds and the workers don't know how to run.

From the "unmanned" control room to the "blocked" evacuation passage, from the smoke detector "wearing a hat" to the fire hydrant "cutting off" and rat droppings - these repeated scenes on site are connected to the same fact: fire-fighting facilities are "everywhere", but everywhere "no one knows how to use, no one is on duty, and no one is maintaining". The safety defense line collapsed in repeated "unknown" situations, and the workers on the assembly line ultimately bore the cost.

During the undercover investigation, the undercover team once said to the company's leaders, which may be worth remembering for every manager: "You focus on production and rushing orders to make money. But if you can't even guarantee the safety of workers, every penny you earn is a loss." Safety is "1", and everything else is "0". Without safety, everything will return to zero.